UNIKOMPENZATOR 400 is active compensator of power factor, in accordance with the requirements of power distribution companies. Maintains the desired power factor by the creation of inductive or capacitive reactive power. Standard control range of power factor cos φ is from 0.95 capacitive to 0.95 inductive (this parameter is configurable for the whole PVP). Active compensator can be supplied even for higher power factor ranges (0.9 capacitive to 0.9 inductive), if requested.

UNIKOMPENZATOR 400 is a transformerless inverter designed for direct connection of a inverter or arbitrary number of parallel ranged inverters on the primary side of the grid transformer with ratio 0.422 kV.

The main advantages of using UNIKOMPENZATOR 400:

UNIKOMPENZATOR UNIKOMPENZATOR UNIKOMPENZATOR

Options:

Basic technical data

  UNIKOMPENZATOR 3F 400/175
Output  
Rated AC power 175 kVA
Rated output current 250 A

Technical data UNIKOMPENZATOR 3f 400

Output voltage 3x 400 V ±10%
Efficiency ≥ 98 %
Output frequency 50 Hz ± 0.5 Hz
cos φ Adjustable from 0.95 capacitive to 0.95 inductive (default = 1)
Total harmonic distortion of the output current (THDi) Max. 3 % at rated current (THD of the network ≤ 1,5%)
RFI filter Inbuilt input DC filter and output AC RFI filter
Control system 32 bit. µP DSP - TI
Communication RS 485, USB, CAN
Communication module - Optional Profibus DP, Modbus RTU, Ethernet, GSM
Contactor at the output YES
Time of disconnection from the grid if the grid is defective ≤ 10 ms
Control panel - Optional Graphic, detachable, programmable
Analog inputs 4 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Analog outputs 3 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Relay output 3 x relay, adjustable, programmable
Protections Current overloading, overvoltage protection of DC inputs and panels , overvoltage protection on the AC side, undervoltage, overvoltage, earth connection on the AC output, cut off between output phases, overheating of the inverter
Cooling Forced air cooling by inbuilt ventilators
Absolute altitude of the permitted usage ≤ 1000 m over the sea, at higher altitude levels reduction of the power for each 100 m of altitude reduction of the inverter power for 1 %
Relative humidity of the air ≤ 95 % without corrosive and explosive gases, without water vapor and condensates
Ambient working temperature + 0 °C to + 40 °C (-20 °C to + 40 °C with optional tempering)
Storage ambient temperature - 25 °C to + 50 °C
Protection IP54
STN EN standards compliance Safety EN 50 178
EMC emissions STN EN 61000-6-1,3
Harmonic distortion:
STN EN 61000 – 3 – 11, STN EN 61000 – 3 – 12
Instructions EEC 2004/108/EEC, 2006/ 95/EEC