UNIFREM 230 E is the latest generation of small dimensions frequency converters family. UNIFREM 230 E is made for 3 x 230 V supply, available up to 1.5 kW. All UNIFREM converters allow high-performance scalar (V/f) control. UNIFREM 230 E drives are designed to solve most of drive problems in the industrial applications. The family is specified by its user-friendly settings and control, users are guided by the graphic display. The latest generation of power electronics has been used for minimization of losses while allowing higher switching frequency. Grid disturbance is kept to a minimum.

Features and advantages of UNIFREM E

UNIFREM 230 E UNIFREM 230 E UNIFREM E

High resistance against fault immiting
UNIFREM converters include protection against overvoltage, undervoltage, current overloading of converter, short circuit between input phases and overheating. Input and output phase loss are detected as well. Overheating of motor is suppressed by calculating the heat integral of the motor.

Minimal disturbance to the supply power grid
Optional input commutation chokes are lowering the harmonic distortion (EN 61800–3). Standard use of noise suppresing filters ensures minimal disturbance to the power grid (EN 61000–6-4).

Minimal losses
Use of the newest power electronics has lowered and minimalized converter losses and power grid disturbance.

Smaller dimensions
By the use of power optimized heat sink together with improved heat-transfer-targeted placement of power components smaller dimensions have been achieved.

High reliability
The latest generation power capacitors with extended operating temperature and lifetime by 20% as well as the newest power electronics components have been used. The cooling fans with high-quality bearings ensure longer lifetime and lower noise level.

Rich software features

Events and faults history
Configurable history of faults, warnings and other events with capacity of latest 256 items.

Commands

Communication with the operators:
Inteligent user interface designed for easy configuration and reliable diagnostic using the inbuilt graphical LCD display.

VONSCH Drive Studio
Application for configuration, diagnostics and archiving of settings to PC. It allows: firmware upgrade, process diagnostic "black box" data. Diagnostics of faults and events helps the operator to solve the problems and avoid the future ones.

Standard equipment:

Noise suppresing filter
Eliminates disturbances to the power grid (EN 61000–6-4)

Brake module
Electronics for brake resistor control used in generator mode of operation

Options:

Single phase commutation choke KT1
Choke Minimization of harmonic currents from the power grid. (EN EN 61800–3)

Motor (output) choke MT1
MT1 Output motor chokes are used in case when the distance between the converter and the motor is higher than 100m (non-shielded cable) or 50m (shielded cable). Cable capacitance effects are eliminated by the motor choke or sine filter.

Brake resistor BO1
Brake resistor Ensures dissipation of kinetic energy in the regenerative mode of motor operation.

Sine filter SF1
Sine filter Sine filter filters the output PWM voltage of the inverter to the sine wave of variable frequency and amplitude. This will limit the peak current and capacitive motor insulation stress. When using the EMC sinus filter, it is not necessary to use the shielded cable. It is necessary to set the switching frequency of IGBT power elements to at least 4 kHz, when using the Sine filter!

Technical data

Type of the converter M ~ constant load Nominal input current of the converter ININ [A]
Motor output rating PNOM [kW] Nominal output current of the converter INK [A] Nominal output current of the converter INK60 [A] Nominal output current of the converter INK2 [A]
UNIFREM 230E 0550 0.55 3.1 4.656.2 7.0
UNIFREM 230E 0750 0.75 4.2 6.3 8.4 9.5
UNIFREM 230E 1100 1.1 5.8 8.7 11.6 13.1
UNIFREM 230E 1500 1.5 7.0 10.514.0 15.8
INK - nominal output current of the converter for constant load
INK60 - nominal output current of the converter that is equalled 1,5 x InK for the duration of 60 s each 10 min
INK2 - maximal output current of the converter that is equalled 2 x InK for the duration of 2 each 15 s

Dimensions

Type of the converter height [mm] width[mm] depth [mm] Inbuilt fan
UNIFREM 230E 0550 ÷ 0750 228 105 122 No
UNIFREM 230E 1100 ÷ 1500 236 105 122 Yes
Up

General technical data

Input voltage range: 1 x 230 V ±10%
Input frequency: 47 to 63 Hz
Output voltage range: 3 x 0 to 100% of input voltage
Output frequency: 0 ÷ 300 Hz
Efficiency of the converter: more than 97.5 %
Analog inputs: 2 configurable analog inputs (Options: 0 ÷ 20 mA , 4 ÷ 20 mA , 0 ÷ 10 V , 2 ÷ 10 V)
Digital inputs: 4 digital configurable inputs
1 digital safety input EN 13849-1 class 3
software adjusted control voltage ( + 24 V or 0 V )
Digital outputs: 2 digital configurable outputs 24V, for connecting to the relay or PLC input
Analog outputs: 1 analog configurable output 0 ÷ 10 V or 2 ÷ 10 V
Starting motor torque: to 150 % Tn (according to the type of motor)
Electronic protection against: overcurrent, overvoltage, undervoltage, short circuit protection, ground fault protection, converter overtemperature, motor overtemperature
Cooling: natural cooling, forced air cooling by built-in fan from Pnom=1.1kW
Electromagnetic compatibility (EMC): Built-in RFI filter to industrial environment according to EN 61000-6-4
Elimination of higher harmonic components of voltages and currents external single phase choke lowers harmonic currents, extends lifetime of power capacitors, protects converter against voltage peaks according to EN 61800-3
Permissible ambient temperature during operation: +1 °C to +40 °C (EN 50178)
Degree of protection: IP20, IP55 possible in enclosure-based modification