FOTO CONTROL 3f CENTRAL is device for transformation of DC voltage generated on the terminals of the solar panel after impact of photons to three phase AC power grid.

FOTO CONTROL 3f CENTRAL is a transformerless inverter designed for direct connection of a inverter or arbitrary number of parallel ranged inverters on the primary side of the grid transformer with ratio 0.29/22 kV.

Inverters of the FOTO CONTROL 3f CENTRAL family are able to work in wide range of input voltage – voltage of photovoltaic cells within the range from 450 V to 800 V at the rated grid voltage. The selection and structure of particular types is made according to specific solar power plant application. The suitable assignment of mentioned types and their number is an ideal solution for solar power plants with total installed power higher than 1 MW.

The main advantages of using FOTO CONTROL 3f CENTRAL:

FOTO CONTROL 3f CENTRAL FOTO CONTROL 3f CENTRAL FOTO CONTROL CENTRAL FOTO CONTROL 3f CENTRAL

Options:

Basic technical data

  FOTO CONTROL 3f CENTRAL / 100 FOTO CONTROL 3f CENTRAL / 125
Output    
Rated AC power 100 kW 125 kW
Rated output current 200 A 250 A
Input    
Rated input current UDC = 600 V 174 A 217 A

Technical data FOTO CONTROL 3f CENTRAL

Peek DC supply voltage 850 V no load
MPPT operating voltage 450 to 800 V
Output voltage 3x 290 V ±10%
Efficiency ≥ 98 %
Euro efficiency ≥ 96.5 %
Output frequency 50 Hz ± 0.5 Hz
cos φ Adjustable from -0.9 capacitive to -0.9 inductive (default = -1)
Total harmonic distortion of the output current (THDi) Max. 3 % at rated current (THD of the grid ≤ 1,5%)
RFI filter Inbuilt input DC filter and output AC RFI filter
Control system 32 bit. µP DSP - TI
Communication RS 485, USB, CAN
Communication module - Optional Profibus DP, Modbus RTU, Ethernet, GSM
Contactor at the output YES
Time of disconnection from the grid if the grid is defective ≤ 10 ms
Control panel - Optional Graphic, detachable, programmable
Analog inputs 4 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Analog outputs 3 /0 (4) – 20 mA/ / 0 (2) – 10 V/
Relay output 3 x relay, adjustable, programmable
Protections Current overloading, overvoltage protection of DC inputs and panels , overvoltage protection on the AC side, undervoltage, overvoltage, earth connection on the AC output, cut off between output phases, overheating of the inverter
Cooling Forced air cooling by inbuilt ventilators
Absolute altitude of the permitted usage ≤ 1000 m over the sea, at higher altitude levels reduction of the power for each 100 m of altitude reduction of the inverter power for 1 %
Relative humidity of the air ≤ 95 % without corrosive and explosive gases, without water vapor and condensates
Ambient working temperature + 0 °C to + 40 °C (-20 °C to + 40 °C with optional tempering)
Storage ambient temperature - 25 °C to + 50 °C
Protection IP54
STN EN standards compliance Safety EN 50 178
EMC emissions STN EN 61000-6-1,3
Harmonic distortion:
STN EN 61000 – 3 – 11, STN EN 61000 – 3 – 12
Instructions EEC 2004/108/EEC, 2006/ 95/EEC