NEXISTORAGE BESS
Battery storage with VONSCH's own BMS and inverter
261 and 522 kWh units with LFP (lithium iron phosphate) cells for industrial sites. The battery and the inverter run on VONSCH firmware developed in Slovakia, so we know what is happening inside the storage system - and we can fix it. An EMS decides when the storage charges and discharges; flexibility trading is handled by a Slovak energy trading partner. The data we process stays in the EU, and security updates are guaranteed under the EU Cyber Resilience Act.
Request a free analysisNot a black box
Most storage systems on the market are finished units whose control nobody in Europe can see from the inside. With NEXISTORAGE, our firmware runs the battery and the inverter - from measuring every cell to the power delivered to the grid. Above them, an EMS decides when the storage charges and discharges.
NEXICONTROL
Three-level bidirectional ANPC inverter in the GSE version for battery storage. The range up to 200 kVA has passed testing at the ČEZ Distribuce laboratory. It stands outside the battery cabinet, so servicing the power section never means opening the battery. NEXICONTROL 400 100-200 →
NEXIBMS
VONSCH's own BMS (Battery Management System) for stationary storage. It measures the voltage and temperature of every cell, controls the contactors and pre-charge, and talks directly to the inverter. The algorithms are tuned for LFP, where the state of charge can hardly be read from the voltage.
EMS
A local EMS guards the reserved grid capacity and PV self-consumption. Flexibility trading is run by the EMS of a Slovak energy trading partner. Both talk to the storage via Modbus TCP. Monitoring via VONSCH Energy Cloud. Who controls what ↓
Who controls what
Control has two layers. The lower one protects the battery and the grid and runs directly in the equipment. The upper one decides on energy trading.
Local control. NEXIBMS guards every cell, the contactors and the pre-charge. NEXICONTROL controls active and reactive power and the grid protection. Both run on VONSCH firmware. A local EMS guards the contracted and maximum reserved grid capacity and manages PV self-consumption.
Trading EMS. Spot and intraday arbitrage and ancillary services are handled by a Slovak energy trading partner, which sends the storage a power setpoint.
When the internet goes down. Battery and grid protection run directly in NEXIBMS and NEXICONTROL, also without internet. Without a link to the higher-level EMS the storage switches to a fallback mode set for the project.
Metering and integration. We supply the metering at the point of common coupling (PCC), or use the existing meter if it has a Modbus interface. The storage connects to a higher-level EMS or SCADA via Modbus TCP or Modbus RTU (RS485). Integration of existing PV is solved in the project design.
European electronics. Our software. Data in the EU.
A battery storage system is part of a site's energy infrastructure. Whoever controls its electronics and software decides whether and when it runs. With NEXISTORAGE, that is an EU manufacturer who can tell you what is inside - and is accountable for it under European rules.
Control electronics from Europe
We design and build both the inverter and the BMS in Brezno, Slovakia. Power semiconductors come from Infineon and the control processor from Texas Instruments - European and US manufacturers with traceable origin.
Software by VONSCH
We write the inverter and BMS firmware and the control algorithms ourselves. The source code is with us, not with a supplier on the other side of the world - so we can find a bug, fix it and ship the fix.
Ready for the CRA
Developed under Regulation (EU) 2024/2847, the Cyber Resilience Act (CRA). Security updates for NEXICONTROL, NEXIBMS and VONSCH Energy Cloud are guaranteed for 15 years from the date the unit is placed on the market. We receive and handle vulnerabilities under our published policy.
Vulnerability disclosure policyData stays in the EU
The operating data we process from the storage system is kept on servers in the EU - VONSCH Energy Cloud runs in Slovakia, with a backup server in Germany. No mandatory manufacturer cloud outside Europe.
Two standard units. The rest is designed to fit.
The battery cabinet and the inverter are separate units connected by a DC cable. Several units are combined on the AC side - from hundreds of kWh up to several MWh.
A storage system should earn money, not just stand there
Reserved capacity
Peak shaving and a lower charge for reserved grid capacity.
PV self-consumption
PV surplus stored for the evening instead of being fed into the grid at zero price.
Flexibility
Participation in flexibility aggregation via a partner EMS.
Backup
Supply of selected circuits during a grid outage - server room, production control.
Technical data
| Parameter | NEXISTORAGE 261 | NEXISTORAGE 522 |
|---|---|---|
| Battery | ||
| Energy | 261 kWh | 522 kWh |
| Battery cabinet | 1 cabinet · 5 packs · 1 string | double cabinet · 10 packs · 2 strings |
| Chemistry | LFP (LiFePO4), 314 Ah cells for stationary storage | |
| Cell lifetime | up to 8,000 cycles to 70 % capacity (cell manufacturer's figure under defined conditions) | |
| String voltage | 832 V nominal · 650 - 949 V operating | |
| C-rate | 0.38C at the inverter's rated power | |
| Cooling | liquid-cooled packs, cabinet dehumidification | |
| Fire protection | detection and aerosol fire suppression inside the cabinet | |
| Protection rating | packs IP67 · cabinet IP54 | |
| Inverter and control | ||
| Inverter | NEXICONTROL 400 100 GSE · 100 kW | NEXICONTROL 400 200 GSE · 200 kW |
| Grid | 3 × 400 V AC | |
| BMS | NEXIBMS - measurement of every cell, contactor and pre-charge control | |
| Communication | CAN between NEXIBMS and the inverter · to EMS / SCADA via Modbus TCP or Modbus RTU (RS485) | |
| EMS | local EMS (reserved capacity, PV self-consumption) · trading EMS - Slovak energy trading partner | |
| Metering at the grid connection point | part of the delivery, or existing metering with a Modbus interface | |
| Monitoring | VONSCH Energy Cloud | |
| Installation | indoor (switch room, plant room, air-conditioned container) · outdoor version with heating | |
| Availability | first deliveries in 2027 | |
Free analysis of your load profile
Send us
- 15-minute load profile for 12 months
- reserved grid capacity (contracted and maximum)
- PV power, if you have PV
- electricity price type: spot or fixed
You get
- recommended size: 261 kWh, 522 kWh or a combination
- estimated savings on reserved capacity and self-consumption
- indicative payback
You can download the profile from your distribution company's portal. If you do not have it at hand, send it later. We will get back to you with a proposal.
Request a free analysis