VQFREM 690 are vector control frequency converters using HDDis of the latest generation. They have been specially designed for the most difficult technical drives applications with induction motors supplied by 3 × 690 V , motor power up to 1400 kW

VQFREM 690

Contents:

VQFREM basic
Optional accessories
Technical data
General technical data
Technical drawings
Library for ELCAD
Software

VQFREM basic

  • electrical enclosure: IP43 protection, input fuses, ventilating unit
  • real time function: enables precise monitoring of converter operation in time, e.g. fault specification
  • built-in control panel "CP": the panel contains alphanumeric 4 x 20 characters display and 9-buttons keypad. The display displays operating instructions in Slovak language and English and the keypad is used for parameters setting and changing
  • RI suppression filter class A1 (according to STN EN 61800-3)
  • commutating reactor "CR": integrated in the frequency converter circuit to reduce current harmonic distortion of power supply. It lengthens the operating life of power capacitors of a converter.
  • inputs: 3 analogue inputs, 6 programmable binary inputs
  • outputs: 2 analogue current outputs: 0 ÷ 20 mA (4 ÷ 20 mA) for output frequency (current) indication
  • two sets of adjusting parameters
  • setting of desired value: binary 8 speeds, reverse, reset, analogue signal 0 ÷ 10 V, 2 ÷ 10 V, or 0 ÷ 20 mA, 4 ÷ 20 mA, potentiometer, external motor - potentiometer
  • adjustable acceleration time (ramp-up time) and deceleration time (ramp-down time)
  • PID process regulator (also reversal function)
  • automatic parking of a converter - if analogue input signal is sufficient and the regulation uses PI process regulator
  • energetic input power optimalization
  • fault history (the converter remembers the latest 10 faults)
  • U/f characteristic for constant and variable motor torque
  • motor braking - 3 braking modes
  • measurement of: fOUT, RPM, UOUT, UIN, IOUT, analogue input
  • modern type SkiiP, SkiiM, IPM - semiconductors, which have lower losses than IGBT. They incorporate an input rectifier and an output inverter and provide complex converter protection (protection against short circuit between output phases, ground faults, overtemperature).
Up

Optional accessories

  • EMC (Electromagnetic compatibility):
    PROFIBUS DP - Vonsch option module PROFIBUS DP enables to control maximum of 99 frequency converters. ID Number: 077 B HEX
    LON - enables frequency converter control via electric power network
    GSM - enables frequency converter control via telecommunication network
    Ethernet - enables frequency converter operation in industrial networks (communication network for industrial applications)
  • external wall control panel "EWCP": it should be wall mounted (the doors of electrical enclosure). EWCP uses RS 422 system to communicate with the converter and can be mounted up to 100m from the converter. The panel contains 4-lines alphanumeric display (displaying in Slovak and English) and 9-buttons keypad.
  • external manual control panel "EMCP": it is designed for manual control of a converter. EMCP enables parameters indication and setting. In addition, it enables that the parameters can be copied from one converter to another. The rest holds as for EWCP.
  • external door control panel "EDCP": it should be mounted on the doors of electrical enclosure. The panel is mounted on the front doors of electrical enclosure so as only membranous keypad is visible and reachable from outside of electrical enclosure. IP55 protection is ensured by this solution. The rest holds as for EWCP.
  • output reactor "OR1" (filter du/dt): it eliminates cable capacitance on frequency converter. Output reactor should be connected to the output terminals U, V, W.
  • higher degree of protection - e.g. IP55, IP66 (frequency converter is built-in electrical enclosure)
Up

Technical data

Power and current:

Converter's losses: temperature losses of frequency converter at sampling frequency 1,5 kHz
Nom. output current of the converter: nominal and maximum permanent output current of the converter
Motor power: recommended maximum power of a motor connectable to converter's output (holds for 4 - pole motors)

Typ meniča Motor output rating Pnom [kW] Converter's losses at 2.5 kHz (kW) Nominal output current of the converter In [A]
VQFREM 690 315 315 7,7 350
VQFREM 690 400 400 9,3 450
VQFREM 690 500 500 12,7 560
VQFREM 690 630 630 15,1 660
VQFREM 690 710 710 16,6 750
VQFREM 690 800 800 18,6 860
VQFREM 690 900 900 21,2 980
VQFREM 690 1000 1000 23,4 1080
VQFREM 690 1200 1200 30 1230
VQFREM 690 1400 1400 34 1470
Up

General technical data

Input voltage range: 690 V ± 10%
Input frequency: 47 - 63 Hz
Power factor: Cos Φ1N > 0,98
Converters efficiency:> 0,975
Output frequency range:0 Hz - 300 Hz
Control system:2 × 32 bit. µP DSP - PWM - HDDiS
Analogue inputs:0 ÷ 20 mA (165 Ω), 4 - 20 mA (165 Ω), 0 - 10 V, 2 - 10 V, potentiometer, motor potentiometer; output voltage + 10 V (short circuit protection) max. 10 mA. Potentiometer 1 kΩ to 10 kΩ
Control inputs and interface: 6 binary inputs for multi-level speed selection, or for remote motor potentiometer, reverse, reset, voltage + 24 V (short circuit protection), max. 100 mA
Analogue outputs:0 ÷ 20 mA, 4 ÷ 20 mA max. 750 Ω
Electronic protection against:overcurrent, overvoltage, undervoltage, short circuit protection, ground fault protection, converter overtemperature, motor overtemperature
Ventilation:fan cooling
Installation altitude:< 1000 m above sea level, each 100 m above 1000 m above sea level causes decrease in converter's power by 1 %
Relative air humidity: < 90 % non-condensing, dewing not permissible
Permissible ambient temperature during operation:+1°C ~ +40°C
Permissible ambient storage temperature: -25°C ~ +50°C