VQFREM 500 are vector control frequency converters using HDDis of the latest generation. They have been specially designed for the most difficult technical drives applications with induction motors supplied by 3 × 500 V, motor power up to 1400 kW.

VQFREM 500 family in all versions is compliant with EU standards and regulations:

EMC (Electromagnetic compatibility):
EMC (Electromagnetic compatibility): STN EN 61800-3
Is compliant with ES Directives: 89/336/EHS, 91/263/EHS, 92/31/EHS, 93/68/EHS, 93/97/EHS
Conforms to SR Government Regulations: 394/1999 Z.z., 159/2002 Z.z.,301/2002 Z.z.
Product safety and conformity:
EMC (Electromagnetic compatibility): EN 50 178, EN 601 46-1 ÷ 3
Conforms to SR Government Regulations: 392/1999 Z.z., 149/2002 Z.z., 303/2002 Z.z.
Is compliant with ES Directives: 73/23EHS, 93/68EHS

VQFREM 500

Contents:

VQFREM basic
Optional accessories
Technical data
General technical data
User guide
Dimensions
Technical drawings
Software
Library for ELCAD

VQFREM basic

  • real time function: enables precise monitoring of converter operation in time, e.g. fault specification
  • built-in control panel "CP": the panel contains alphanumeric 4 x 20 characters display and 9-buttons keypad. The display displays operating instructions in Slovak language and English and the keypad is used for parameters setting and changing
  • RI suppression filter class A1 (according to STN EN 61800-3)
  • commutating reactor "CR": integrated in the frequency converter circuit to reduce current harmonic distortion of power supply. It lengthens the operating life of power capacitors of a converter.
  • inputs: 3 analogue inputs, 6 programmable binary inputs
  • outputs: 3 programmable output relays 230 V / 3 A (e.g. fault, READY...)
  • two sets of adjusting parameters
  • setting of desired value: binary 8 speeds, reverse, reset, analogue signal 0 ÷ 10 V, 2 ÷ 10 V, or 0 ÷ 20 mA, 4 ÷ 20 mA, potentiometer, external motor - potentiometer
  • adjustable acceleration time (ramp-up time) and deceleration time (ramp-down time)
  • PID process regulator (also reversal function)
  • automatic parking of a converter - if analogue input signal is sufficient and the regulation uses PI process regulator
  • energetic input power optimalization
  • fault history (the converter remembers the latest 10 faults)
  • U/f characteristic for constant and variable motor torque
  • motor braking - 3 braking modes
  • measurement of: fOUT, RPM, UOUT, UIN, IOUT, analogue input
  • modern type SkiiP, SkiiM, IPM - semiconductors, which have lower losses than IGBT. They incorporate an input rectifier and an output inverter and provide complex converter protection (protection against short circuit between output phases, ground faults, overtemperature).
Up

Optional accessories

  • EMC (Electromagnetic compatibility):
    PROFIBUS DP - Vonsch option module PROFIBUS DP enables to control maximum of 99 frequency converters. ID Number: 077 B HEX
    LON - enables frequency converter control via electric power network
    GSM - enables frequency converter control via telecommunication network
    Ethernet - enables frequency converter operation in industrial networks (communication network for industrial applications)
  • external wall control panel "EWCP": it should be wall mounted (the doors of electrical enclosure). EWCP uses RS 422 system to communicate with the converter and can be mounted up to 100m from the converter. The panel contains 4-lines alphanumeric display (displaying in Slovak and English) and 9-buttons keypad.
  • external manual control panel "EMCP": it is designed for manual control of a converter. EMCP enables parameters indication and setting. In addition, it enables that the parameters can be copied from one converter to another. The rest holds as for EWCP.
  • external door control panel "EDCP": it should be mounted on the doors of electrical enclosure. The panel is mounted on the front doors of electrical enclosure so as only membranous keypad is visible and reachable from outside of electrical enclosure. IP55 protection is ensured by this solution. The rest holds as for EWCP.
  • output reactor "OR1" (filter du/dt): it eliminates cable capacitance on frequency converter. Output reactor should be connected to the output terminals U, V, W.
  • sinusoidal output filter "SF1" - ensures converter output voltage to reach the desired sine waveform. If there is minimum radio interference emission demand (e.g. theatres), screened interconnecting cables between a converter and a motor do not have to be used when using sinusoidal output filter. Sinusoidal output filter completely eliminates overvoltage spikes on output (motor) terminals. It can be connected directly to the output terminals of frequency converter. If using sinusoidal output filter, it is necessary to set sampling frequency (parameter 9.1.1) rating from 5 ÷ 10 kHz and frequency converter cannot operate in vector control mode.
  • higher degree of protection - e.g. IP55, IP66 (frequency converter is built-in electrical enclosure)
Up

Technical data

Power and current:

Nom. input current of the converter InIN :effective input current of the converter ( depends from cos Φ of a motor and other)
Nom. output current of the converter:nominal and maximum permanent output current of the converter
Motor power: recommended maximum power of a motor connectable to converter's output (holds for 4 - pole motors)

InQ - nominal output current of the converter for variable load
InL - nominal output current of the converter for constant load
InL60 - maximal output current of the converter that is equalled 1,5 x InL for the duration of 60 s each 10 min (this relates only to constant load)
InL2 - maximal output current of the converter that is equalled 2 x InL for the duration of 2 each 15 s (this relates only to constant load)

The type of the converter M ~ variable load M ~ constant load
Motor output rating Pnom [kW] Nominal output current of the converter InQ [A] Motor output rating Pnom [kW] Nominal output current of the converter Inl Maximal output current of the converter InL60 [A] Maximal output current of the converter InL2[A]
VQFREM 500 015 15 26,5 11 19 29 38
VQFREM 500 018 18,5 32 15 26,5 39,5 53
VQFREM 500 022 22 37,5 18,5 32 48 64
VQFREM 500 030 30 50 22 37,5 56 75
VQFREM 500 037 37 60 30 50 75 100
VQFREM 500 045 45 72 37 60 90 120
VQFREM 500 055 55 90 45 72 108 144
VQFREM 500 075 75 116 55 90 135 180
VQFREM 500 090 90 140 75 116 174 232
VQFREM 500 100 100 156 90 140 210 280
VQFREM 500 110 110 173 100 156 234 312
VQFREM 500 132 132 208 110 173 260 346
VQFREM 500 160 160 252 132 208 312 416
VQFREM 500 200 200 317 160 252 378 504
VQFREM 500 315 315 484 237 363 545 726
VQFREM 500 400 400 622 301 467 700 933
VQFREM 500 500 500 773 376 580 870 1160
VQFREM 500 630 630 897 474 673 1009 1346
VQFREM 500 710 710 1035 534 776 1164 1553
VQFREM 500 800 800 1187 602 890 1335 1781
VQFREM 500 900 900 1353 677 1015 1522 2030
VQFREM 500 1000 1000 1491 752 1118 1677 2237
VQFREM 500 1200 1200 1698 902 1274 1910 2547
VQFREM 500 1400 1400 2029 1053 1522 2283 3044
Up

General technical data

Input voltage range: 500 V ± 10%
Input frequency: 47 - 63 Hz
Power factor: Cos Φ1N > 0,98
Converters efficiency:> 0,975
Output frequency range:0 Hz - 300 Hz
Control system:2 × 32 bit. µP DSP - PWM - HDDiS
Analogue inputs:0 ÷ 20 mA (165 Ω), 4 - 20 mA (165 Ω), 0 - 10 V, 2 - 10 V, potentiometer, motor potentiometer; output voltage + 10 V (short circuit protection) max. 10 mA. Potentiometer 1 kΩ to 10 kΩ
Control inputs and interface: 6 binary inputs for multi-level speed selection, or for remote motor potentiometer, reverse, reset, voltage + 24 V (short circuit protection), max. 100 mA
Analogue outputs:0 ÷ 20 mA, 4 ÷ 20 mA max. 750 Ω
Starting motor torque: to 200 % Mn (according to the type of motor)
Electronic protection against:overcurrent, overvoltage, undervoltage, short circuit protection, ground fault protection, converter overtemperature, motor overtemperature
Ventilation:fan cooling
Installation altitude:< 1000 m above sea level, each 100 m above 1000 m above sea level causes decrease in converter's power by 1 %
Relative air humidity: < 90 % non-condensing, dewing not permissible
Permissible ambient temperature during operation:+1°C ~ +40°C
Permissible ambient storage temperature: -25°C ~ +50°C
Up

Technical drawings

Drawing FormatSize
Connection of cables between RM - PBDP and PROFIBUS for RS-485 PDF 27 kB
Connection of cables between VQFREM 400 S and RM-PB DP PDF 36 kB
Extension module for connecting the frequency converter to Profibus PDF 35 kB
Up

Dimensions

The type of the converter height [mm] width[mm] depth [mm] weight [kg]
VQFREM 500 015 ÷ 030 661 265 272 29
VQFREM 500 037 ÷ 075 740 304 307 35
VQFREM 500 090 ÷ 110 1050 364 381 80
VQFREM 500 132 ÷ 200 1200 464 381 115
VQFREM 500 315 ÷ 800 2200 1800 600 400
VQFREM 500 1000 ÷ 1400 2200 1800 600 800