GSE COMP
GSE COMP 400 is a transformerless inverter designed for direct connection of an inverter or arbitrary number of parallel ranged inverters on the primary side of the grid transformer with ratio 0,4/XX kV.
GSE COMP inverters do not allow off-grid operation.
GSE COMP 400 serves as a battery-fed bidirectional inverter for 400V three-phase power system. VONSCH GSE COMP 400 is the ideal product to provide the following:
- Peak-shaving
with a proper control, GSE COMP can be used to reduce maximum power peaks - Reactive power compensation
thanks to the measurement of currents and load voltages, the total reactive power of the system can be continuously and quickly controlled - Frequency control
Frequency control is only relevant in small island networks called "microgrid", where surplus or lack of power is reflected in an increase or decrease of the grid frequency (droop control) - Charging / discharging and forming the battery
Thanks to the fast control of the DC current (battery current), the inverters can be used to charge and recharge batteries with very high efficiency
Features:
- High efficiency
- Fast start-up
- Fast reaction time to step change of load
- Long durability of device
- Ecological device – minimal consumption in standby
Basic technical data
| GSE COMP 400 / 10 | GSE COMP 400 / 20 | GSE COMP 400 / 33 | GSE COMP 400 / 50 | GSE COMP 400 / 99 | GSE COMP 400 / 100 | GSE COMP 400 / 125 | |
|---|---|---|---|---|---|---|---|
| AC Output | |||||||
| Rated AC power Pnom | 10 kVA | 20 kVA | 33 kVA | 50 kVA | 99 kVA | 100 kVA | 125 kVA |
| Rated output current Inom | 14.5 A | 29 A | 48 A | 73 A | 143.5 A | 145 A | 180 A |
| Maximum output current Imax (2s every 30s) | 21.25 A | 43.5 A | 72 A | 109 A | 215 A | 217 A | 270 A |
| DC Input | |||||||
| Rated input voltage VBATnom | 750 VDC | 750 VDC | 750 VDC | 750 VDC | 750 VDC | 750 VDC | 750 VDC |
| Min. input voltage VBATmin | 630 VDC | 630 VDC | 630 VDC | 630 VDC | 630 VDC | 630 VDC | 630 VDC |
| Max. input voltage VBATmax | 835 VDC | 835 VDC | 835 VDC | 835 VDC | 835 VDC | 835 VDC | 835 VDC |
| Rated input current IINnom (at VBATnom ) | 16.4 A | 33 A | 55 A | 82 A | 162 A | 164 A | 205 A |
| Dimensions (w x h x d) | 600x800x350 mm | 600x1100x400 mm | 800x1300x500 mm | 800x1800x500 mm | 800x1800x500 mm | 800x1800x500 mm | 800x1800x500 mm |
| Weight | 75 kg | 150 kg | 200 kg | 240 kg | 300 kg | 300 kg | 300 kg |
Technical data
| Output voltage | 3x 400 V ±10% |
|---|---|
| Efficiency | ≥ 97.5 % |
| Output frequency | 50 Hz ± 0.5 Hz |
| cos φ | Adjustable from 0.9 capacitive to 0.9 inductive (default = 1) |
| Total harmonic distortion of the output current (THDi) | Max. 3 % at rated current (THD of the grid ≤ 1,5%) |
| RFI filter | Inbuilt input DC filter and output AC RFI filter |
| Control system | 32 bit. µP DSP - TI |
| Communication | RS 485, USB, CAN |
| Communication module - Optional | Profibus DP, Modbus RTU, Ethernet, GSM |
| Contactor at the output | YES |
| Time of disconnection from the grid if the grid is defective | ≤ 10 ms |
| Control panel - Optional | Graphic, detachable, programmable |
| Analog inputs | 4 /0 (4) – 20 mA/ / 0 (2) – 10 V/ |
| Analog outputs | 3 /0 (4) – 20 mA/ / 0 (2) – 10 V/ |
| Relay output | 3 x relay, adjustable, programmable |
| Protections | Current overloading, overvoltage protection of DC inputs and panels , overvoltage protection on the AC side, undervoltage, overvoltage, earth connection on the AC output, cut off between output phases, overheating of the inverter |
| Cooling | Forced air cooling by inbuilt ventilators |
| Absolute altitude of the permitted usage | ≤ 1000 m over the sea, at higher altitude levels reduction of the power for each 100 m of altitude reduction of the inverter power for 1 % |
| Relative humidity of the air | ≤ 95 % without corrosive and explosive gases, without water vapor and condensates |
| Ambient working temperature | + 0 °C to + 40 °C (-20 °C to + 40 °C with optional tempering) |
| Storage ambient temperature | - 25 °C to + 50 °C |
| Protection | IP54 |
| STN EN standards compliance | Safety EN 50178 Grid quality: EN 50160 EMC emissions: EN 61000-6-2,4, EN 55011 Harmonic distortion: EN 61000–3–11, EN 61439-1,2 |
| Instructions EEC | 2014/35/EEC, 2014/ 30/EEC, 2011/65/EEC, 2015/863/EEC |