SINAM Softstarts

The SINAM 400 softstarts are used to control the start-up and run-up of an asynchronous motor by changing the amplitude of the clamp voltage.

Models

The latest generation of softstarts

Almost linear start-up and engine run-up over time
Designed for 3 × 400 V motors in the power range 3 to 500 kW
SINAM 400

Characteristics and advantages of SINAM

Smooth start-up and catch-up

The SINAM 400 enables the gentle starting and stopping of asynchronous motors by gradually increasing and decreasing the clamp voltage using phase control, ensuring smooth and controlled start and stop.

Precise control with DSP

The DSP microprocessor, together with torque waveform modelling based on current, voltage and power factor measurements, enables near-linear motor start-up and coast-down, optimising performance and protecting the device.

Wiring flexibility

Customers can choose between a classic (mains – softstart – motor) and a DELTA configuration, with internal current measurement eliminating the need for additional thermal protection of the motor.

Mechanical advantages

The use of a soft start reduces the torque, which eliminates shocks in the mechanical system, extends the life of the clutches and eliminates the need for star-delta switching.

Electrical advantages

The SINAM 400 reduces the inrush current to a set level (2.5 to 4 times the nominal current), minimizing wear on contactor contacts and reducing the number of switching devices required compared to traditional star-delta start-up.

Rich standard equipment

The device features 32-bit DSP control and a three-digit LED display with setpoints, programmable binary and analog inputs and outputs, allowing for complex configuration and the ability to cascade control of multiple motors.

Energy efficiency and diagnostics

The SAVING ENERGY functions of power optimization, voltage boost setting at the start of start-up and display of key parameters (current, power, input, mains frequency) ensure efficient use of energy and allow detailed diagnostics of the motor status.

Wide application possibilities

Designed for 3 × 400 V asynchronous motors with power ratings from 3 to 500 kW, the SINAM 400 is ideal for controlling the starting torque of fans, pumps, conveyors and other applications where it is necessary to control a motor with a higher starting torque than the required starting torque of the mechanical system.

Standard equipment

Control by 32 bit DSP

32 bit DSP control, built-in three-digit LED display with adjustment elements

Softstart current limitation

The softstart current limit is set to 5 times the nominal current of the In softstart.

Adjustable motor current limitation

Adjustable motor current limitation in the range of 50 to 550% of the nominal motor current InM

Automatic check for power phase failure

Near-linear start-up and engine run-up settings

Adjustable thermal integral motor

Additional equipment

Higher protection up to IP66

Ventilation unit

The ventilation unit is assigned to the SINAM 400 for the following reasons:

for triggering more frequently than specified in the TECHNICAL DATA
in voltage-limited operation
in operation without override contactor
in operation with aic start-up – running at current limit
in “energy optimisation” operation

Technical data

Standard connection between mains and motorDELTA connection
Normal operation*Heavy Duty**Normal operation*Heavy Duty**Dimension
Type of soft startNom. current (A)Engine power (kW)Engine power (kW)Engine power (kW)Engine power (kW)height [mm]width [mm]hĺbka [mm]
SINAM 400/99435,54295165175
SINAM 400/12125,547,55,5295165175
SINAM 400/17177,55,5117,5295165175
SINAM 400/2323117,518,511295165175
SINAM 400/323215112218,5295165175
SINAM 400/444422153722295165175
SINAM 400/606030224537350165175
SINAM 400/747437305545350165175
SINAM 400/919145377555350165175
SINAM 400/11211255459075415310250
SINAM 400/145145755511090415310250
SINAM 400/21021011075160110415310250
SINAM 400/252252132110200160685400285
SINAM 400/310310160132250200685400285
SINAM 400/380380200160315250685400285
SINAM 400/480480250200400315685400285
SINAM 400/598598315250500400685400285
* Normal operation with normal load (pumps and fans)
** Severe operation with high load (crusher, mill, press, conveyor, tow)

Do you need a soft start of a similar type or focus, but outside the scope of the table?

General technical data

Supply voltage:400 V -15% to +10%
Frequency e.g. voltages:50 Hz ± 1 %
Softstart efficiency:> 0.975 during start-up, when bridged by a contactor > 0.99
Output voltage:0 to supply voltage
Control system:32 bit. DSP
Input input analog signal:0 ÷ 20 mA (250 Ω), 4 ÷ 20 mA (250 Ω), 0 ÷ 10 V, 2 ÷ 10 V, potentiometer, motor potentiometer; output voltage + 10 V (short-circuit proof) loadable max. 10mA. Potentiometer 1 kΩ to 10 kΩ
Contact inputs:4 binary inputs for multi-step speed entry, or for remote motor potentiometer, reset, voltage +24 V (short-circuit proof) on 1:X1 load max. 100mA
Output. analog signal:0 ÷ 20 mA, 4 ÷ 20 mA max. 750 Ω - for indicating the softstart output voltage, or output current
Current limit:software adjustable in the range: 50 ÷ 550% of the motor current
Current. softstart limitation:5 x In, where In is the nominal current of the softstart
Ramp start times:two sections of increasing - rise of the output voltage, each section adjustable in time from 1 ÷ 300 s
Ramp run-up times:two sections of output voltage reduction - catch-up, each section adjustable in time from 1 ÷ 300 s
Electronic inverter protections:current overload, overvoltage in the network, undervoltage in the network, thermal integral of the motor, thermal overheating of the softstart
Cooling:ambient air, OPTION - ventilation unit
Altitude of permitted deployment:< 1000 m above sea level, at higher altitudes reduction of converter power to every 100 m above 1000 m above sea level reduction of converter power by 1%
Relative air humidity:< 90% without corrosive and explosive gases, without water vapor and condensates
Ambient working temperature:+ 1 °C to + 40 °C
Ambient storage temperature:- 25 °C to + 50 °C
Allowed vibrations:0,7 g ( 10 Hz ÷ 100 Hz )
Coverage:SINAM 400/9 - 191 IP 20
SINAM 400/252 - 598 IP 00

Support

Close Menu
Privacy Policy
VONSCH.SK

Cookies are small text files that are saved on the disk of your computer when you visit a website that uses them. On your next visit, the given website has the possibility to read and use the information stored in the given cookies to improve your experience of using the given website.

You can change your cookie settings in individual tabs, or you can enable all cookies by clicking the "Enable all" button.

Strictly Necessary Cookies

These cookies ensure the proper functioning of our website, for example, they ensure the function of logging into the user account on the site, storing goods in the shopping cart, or they detect attempts at unauthorized login to the account. Without these cookies, our website would not function properly, their use is necessary and therefore we do not ask for your consent to their use.

Analytics

We use these cookies to analyse traffic. This will allow us to improve the content and appearance of the website so that you can find the information you are looking for quickly and easily. We store cookies of this type only based on your consent.

Marketing

We use these cookies so that we can show you content on our site that is of interest to you according to your previous preferences, and also for the purpose of displaying advertising based on your interests. We store cookies of this type only based on your consent.